EasyManua.ls Logo

GE STD15C - Page 13

GE STD15C
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEK—45307
Any
current
of
distorted,
nonsinusoidal
waveform
may
be
considered
as
being
composed
of
a
DC
component
plus
a
number
of
sine-wave
components
of
different
frequencies;
one
of
the
fundamental
system
frequency,
and
the
others,
called
“harmonics,”
having
frequencies
which
are
2,
3,
4,
5,
etc.,
times
the
fundamental
frequency.
The
relative
magnitudes
and
phase
positions
of
the
harmonics
with
reference
to
the
fundamental
determine
the
waveform.
When
analyzed
in
this
manner,
the
typical
fault-current
wave
is
found
to
contain
only
a
very
small
percentage
of
harmonics,
while
the
typical
magnetizing-inrush—current
wave
contains
a
considerable
amount.
The
high
percentage
of
harmonic
currents
in
the
magnetizing-inrush—current
wave
afford
an
excellent
means
of
distinguishing
it
electrically
from
the
fault-current
wave.
In
the
Type
STD
relays,
the
harmonic
components
are
separated
from
the
fundamental
component
by
suitable
electric
filters.
The
harmonic
current
components
are
passed
through
the
restraining
circuit
of
the
relay,
while
the
fundamental
component
is
passed
through
the
operating
circuit.
The
DC
component
present
in
both
the
magnetizing-inrush—
and
offset-fault—current
waves
is
largely
blocked
by
the
auxiliary
differential-current
transformer
inside
the
relay,
and
produces
only
a
slight
momentary
restraining
effect.
Relay
operation
occurs
on
differential-current
waves
in
which
the
ratio
of
harmonics
to
fundamental
is
lower
than
a
given
predetermined
value,
for
which
the
relay
is
set
(e.g.
an
internal
fault—current
wave),
and
is
restrained
on
differential—current
waves
in
which
the
ratio
exceeds
this
value
(e.g.
magnetizing-inrush—current
wave).
BURDENS
Burdens
are
shown
in
Table
III
and IV.
Burdens
and
minimum
pickup
values
are
substantially
independent
of
the
percent
slope
settings,
and
are
all
approximately
100%
power
factor.
Figures
given
are
burdens
imposed
on
each
current
transformer
at
5.0
amperes.
TABLE
III
ZERO
OPERATING
CIRCUIT
*
RESTRAINT
CIRCUIT
TA
G
RESTRAINT
60
CYCLE
RELAYS
60
CYCLE
RELAYS
SETTIN
PICKUP
BURDEN
IMPEDANCE
BURDEN
IMPEDANCE
AMPS
AMPS
VA
OHMS
VA
OHMS
2.9
0.87
3.2
0.128
1.3
0.052
3.2
0.96
2.7
0.108
1.2
0.048
3.5
1.05
2.4
0.096
1.1
0.044
3.8
1.14
2.0
0.080
1.0
0.040
4.2
1.26
1.9
0.076
0.9
0.036
4.6
1.38
1.6
0.064
0.8
0.032
5.0
1.50
1.5
0.060
0.7
0.028
8.7
2.61
0.7
0.028
0.5
0.020
*
Burden
of
operating
coil
is
0
under
normal
conditions.
Burden
of
50-cycle
relay
is
the
same
or
slightly
lower.
TABLE
IV
DC
CONTROL
CIRCUIT
BURDEN
RATED
VOLTS
48
125
250
48
110
220
MILLIANPS
140
105
88
140
96
80
13

Related product manuals