GEK-98834B
7
7(&+1,&$/&+$5$&7(5,67,&6
7HPSHUDWXUH5DQJH
Operating: 14 °F to 131 °F (-20 °C to +55 °C)
Storage: -40 °F to 149 °F (-40 °C to +65 °C)
,QVXODWLRQ7HVW
Between any terminal and ground:
2 kV, 50/60 Hz, 1 min duration.
Between independent circuits:
2 kV, 50/60 Hz, 1 min duration.
2SHUDWLQJ5DQJH'HSHQGLQJRQWKH'LIIHUHQW0RGHOV
20 to 275 VAC in 1V steps
50 to 305 VAC in 1V steps
3 to 66 VAC in 1V steps
$X[LOLDU\3RZHU6XSSO\
Rated Voltage VDC/VAC Operating Range VDC/VAC
24/48 19/58
48/125 38/150
110/240 88/288
If the power supply falls below the values listed in the table, the relay disconnects
automatically and activates a “power supply alarm” auxiliary contact.
The power supply variation included in the ranges established by the table cause a
variation in the operating margins not greater than 3%. The relay consumption is less
that 3W for any power supply value.
7ULS&RQWDFW&DSDFLW\
Continuous: 3A
Make and carry: 30A
Break: 180 VA resistive at 125/250 VDC
60 VA inductive at 125/250 VDC.