EasyManua.ls Logo

GE TOV

GE TOV
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEK-98834B
8
$X[LOLDU\&RQWDFWV&DSDFLW\
Continuous: 3 A
Make and carry: 5 A during 30 s.
Break: 25 W inductive at 125/250 VDC
Carry continuously: 20 W maximum of 250 VDC or 5 A.
$FFXUDF\
Voltage: ±5%
Time: ±5% or 30 ms (whichever is greater).
$PELHQW+XPLGLW\
Up to 95% without condensation.
)UHTXHQF\5DQJH
SINGLE PHASE THREE PHASE
Rated frequency 50 or 60 Hz 50/60 Hz
Effective range 48/51 Hz or 57/63 Hz 48/63 Hz
Operative range 46/53 Hz or 56/64 Hz 46/64 Hz
%XUGHQV
20-275 VAC and 50-305 VAC ranges 3-66 VAC range
Tap set to 50 VAC Tap set to 5 VAC
V (VAC) VA V(VAC) VA
30 0.012 5 0.019
120 0.100 25 0.022
210 0.291 45 0.053
300 0.783 65 0.092
0D[LPXP9ROWDJH
Ranges 20-275 VAC and 50-305 VAC: 400 VAC continuously.
Range 3-66 VAC 200 VAC Continuously.