CONNECT SERIES SERVICE MANUAL
7
ENGLISH
Settings
Outdoor Unit PCB (UUC136WC*/UUC148WC* Only)
SW1-1 SW1-3
800 rpm OFF ON
830 rpm ON ON
830 rpm ON OFF
900 rpm (default) OFF OFF
SW1-2
380V, 3 ph ON
220V, 1 ph (default) OFF
SW1-4
154°F (68°C) / 126°F (52°C) ON
149°F (65°C) / 118°F (48°C) (default) OFF
Example:
When T3 is over 154°F (68°C), unit will stop.
When T3 is lower than 126°F (52°C), unit will run.
Select Fan Speed (SW1-1 & SW1-3)
Select Power Supply (SW1-2)
Select Condenser Protection Temperature
and Recovery Temperature (SW1-4)
SW1
(Shown in default
configuration - all
switches OFF)