6-18 VersaMax Modules, Power Supplies and Carriers GFK-1504N
6
IC200ERM002
Expansion Receiver Module, Non-isolated
Module Specifications
Module Characteristics
LED indicators PWR LED indicates 5 V DC power status
EXP RX LED indicates expansion bus communications status
SCAN LED indicates whether the CPU/NIU is scanning I/O in
Backplane current
5V output: 70mA maximum
FW version #
No
No
Cable Specifications
Maximum cable length
Effective data rate
15 meters (differential) , 1 m (single-ended)
5 Mbits/sec (differential), 2.765 Mbits/sec (single-ended)
Non-isolated differential or single-ended communications
Catalog Numbers
Expansion Cable,
Shielded
Terminator Plug
IC200CBL601 - 1 m
IC200CBL602 - 2 m
IC200CBL615 - 15 m
IC200ACC201 (included with ETM)
Modules for Expansion Racks
All I/O and communications modules can be used in expansion racks. Some
analog modules require specific module revisions as listed below. The date
code is a 3-digit number on the outside of the module and on the shipping box.
IC200ALG230 A or later
CPU or NIU Revision 1.5: Date code must begin with a
number other than 9 and must be 011 or greater.
CPU or NIU Revision 2.0 or later: Any date code.
CPU or NIU Revision 1.5: Date code must begin with a
number other than 9 and must be 011 or greater.
CPU or NIU Revision 2.0 or later: Any date code.