8-14 VersaMax Modules, Power Supplies and Carriers User's Manual GFK-1504N
8
IC200MDL331
Output Module, 120 V AC 2.0 A, Isolated 8 Points
Thermal Derating
The number of points that can be on at the same time depends on the ambient
temperature, the output current, and the orientation of the module and DIN rail.
The following charts display thermal deratings for the module at 120 V AC with
the indicated output current per point.
Number of Points On At the Same Time
Number of Points On At the Same Time
Examples of Combining 2A and 0.5A Outputs
Number of 2 A Points and Number of 0.5A
Points
60deg C 1 + 0
50deg C 1 + 5
40deg C 2 + 2
40deg C 1 + 7