GFK-1504N Chapter 8 Discrete Output Modules 8-43
IC200MDL930
Output Module, Relay 2.0 A Isolated Form A 8 Points
Module Specifications
Points 8 individually isolated Form A relay outputs
Module ID FFFF8040
Isolation:
User input to logic (optical)
and to frame ground
Group to group
250 V AC continuous; 1500 V AC for 1 minute
Not applicable
250 V AC continuous; 1500 V AC for 1 minute
LED indicators One LED per point shows individual point ON/OFF status
OK LED indicates backplane power is present
Backplane current
5 V output: 245mA maximum. See graph
External power supply 0 to 125 V DC, 5/24/125 V DC nominal
0 to 265 V AC (47 to 63Hz), 120/240 V AC nominal
Compatibility
Cimplicity
ME
Versa
Pro
Control
90
CPU
001
CPU
002
CPU
005
CPU
E05
DBI
001
EBI
001
GBI
001
PBI
001
HW,FW vers.
FW release
2.11 1.0 2.2
Output voltage 0 to 125 V DC, 5/24/125 V DC nominal
0 to 265 V AC (47 to 63Hz), 120/240 V AC nominal
Load current 10mA per point minimum
2.0A for 5 to 265 V AC maximum (resistive)
2.0A for 5 to 30 V DC maximum (resistive)
0.2A for 31 to 125 V DC maximum (resistive)
Not applicable (open contact)
On response time
10ms maximum
No internal fuses or snubbers
20 cycles per minute (inductive load)
Fixed coil, moving armature