GFK-1504N Chapter 9 Discrete Mixed Modules 9-41
9
IC200MDD848
Mixed Module, Output 120 V AC 0.5A per Pt Isolated 8 Points /
Input 120 V AC Grouped 8 Points
Thermal Derating
The number of points that can be on at the same time depends on the ambient
temperature, the external voltage, and the orientation of the module and DIN rail.
The following charts display thermal deratings for this module at 120 V AC and
132 V AC. The shaded bands are temperature ranges that represent allowable
combinations of inputs points for the indicated number of outputs points. All
combinations of points are permissible at lower temperatures. The narrow white
line within each range shows maximum temperature when the number of output
points equals the number of input points that are on at the same time.
Ambient Temperature
Output Points On At the Same Time
60ºC
50ºC
55ºC
45ºC
40ºC
35ºC
8
6
4
2
7
5
3
1
120VAC
All
combinations
of points OK
Maximum
with 8 inputs
ON
Maximum with
0 inputs ON
Output Points On At the Same Time
Ambient Temperature
60ºC
50ºC
55ºC
45ºC
40ºC
35ºC
30ºC
8
6
4
2
7
5
3
1
132VAC
All
combinations
of points OK
Maximum
with 8 inputs
ON
Maximum with
0 inputs ON
Ambient Temperature
Output Points On At the Same Time
60ºC
50ºC
55ºC
45ºC
40ºC
35ºC
8
6
4
2
7
5
3
1
120VAC
All
combinations
of points OK
Maximum
with 8 inputs
ON
Maximum with
0 inputs ON
Ambient Temperature
Output Points On At the Same Time
60ºC
50ºC
55ºC
45ºC
40ºC
35ºC
30ºC
8
6
4
2
7
5
3
1
132VAC
All
combinations
of points OK
Maximum
with 8 inputs
ON
Maximum with
0 inputs ON

Table of Contents