GFK-1504N Chapter 9 Discrete Mixed Modules 9-49
9
IC200MDD850
Mixed Module, Output Relay 2.0 A per Pt Isolated 8 Points /
Input 240 V AC Isolated 4 Points
Field Wiring
Terminal
Connection
Terminal
Connection
A1
Output 1-1
B1
No connection
A2
Output 1-2
B2
No connection
A3
Output 2-1
B3
Input 1
A4
Output 2-2
B4
Input 1 Return
A5
Output 3-1
B5
No connection
A6
Output 3-2
B6
No connection
A7
Output 4-1
B7
Input 2
A8
Output 4-2
B8
Input 2 Return
A9
Output 5-1
B9
No connection
A10
Output 5-2
B10
No connection
A11
Output 6-1
B11
Input 3
A12
Output 6-2
B12
Input 3 Return
A13
Output 7-1
B13
No connection
A14
Output 7-2
B14
No connection
A15
Output 8-1
B15
Input 4
A16
Output 8-2
B16
Input 4 Return
A17
No connection
B17
No connection
A18
No connection
B18
No connection
Outputs are individually isolated. This module should be used with a compact
terminal-style carrier (IC200CHS022 or 025) or with a terminal-style carrier
(IC200CHS001, 002, 005 suffix “B” or higher). It cannot be used with a Connector-
Style Carrier (IC200CHS003) due to its high isolation requirement. When wiring
outputs to inductive loads, use of external suppression circuits is recommended.
Refer to chapter 2, Installing Wiring for I/O Devices-Wiring to Inductive Loads.
Wiring Connections
for Carriers with Two
Rows of Terminals
IC200CHS002, 005
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
v
v
v
v
v
v
v
v
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
10
10
B
A
I1
I2
I3
I4
N
H
N
H
N
H
N
H
Wiring Connections
for Carriers with
Three Rows of
Terminals
IC200CHS001, 022, 025
N
H
1
2
3
4
5
6
1
2
3
4
5
6
13
14
15
16
17
18
7
8
9
11
12
10
A
13
14
15
16
17
18
7
8
9
11
12
10
B
Q4
Q5
Q6
Q7
Q8
v
v
v
v
v
Q1
Q2
Q3
v
v
v
I1
I2
I3
I4
N
H
N
H
N
H