GFK-1504N Chapter 10 Analog Input Modules 10-11
IC200ALG240
Analog Input Module, 16 Bit Voltage/Current, 1500 V AC Isolation, 8 Channels
Field Wiring
A 24 volt power supply must be connected to A17 and A18 to operate the
module. The power wiring does not require shielding. Current inputs are applied
with positive current flow into VININn+ and out of IINn-. Both negative terminals
IINn- and VINn- of the channel should be connected together for best accuracy
on current ranges. Voltage inputs are applied between VININn+ and VINn- with
positive to VININn+.
Wiring Connections
for Carriers with Two
Rows of Terminals
IC200CHS002, 005
IC200CHS012, 015
Wiring Connections
for Carriers with
Three Rows of
Terminals
IC200CHS001, 022, 025
IC200CHS011