GFK-1504N Chapter 10 Analog Input Modules 10-33
IC200ALG262
Analog Input Module, 15 Bit Differential Current 8 Channels
Scaling
The following figure illustrates the relationship between the input current
measured at the field terminals and the data that is output by the module.
0 8192 16384 24576 32767
Count
The following equations can be used to calculate count values:
4-20mA Range: Counts = (Current in mA - 4mA) x (32000 / 16mA)
0-20mA Range: Counts = (Current in mA ) x (32000 / 20mA)
Note 1: In 4-20mA mode, signal inputs below 4.077mA are converted to zero counts.
Note 2: In 4-20mA mode, signal inputs at 20.000mA or above 20.383mA are
converted to 32000 counts.
Operating Range