GFK-1504N Chapter 10 Analog Input Modules 10-43
10
IC200ALG264, IC200ALG266
Analog Input Module, 15 Bit Current 15 Channels
Jumper Selections
A jumper selects the current input range.
Jumper
Range
None
4-20mA
Installed from A16 to A17
0-20mA
Wiring Examples
I 13
I 2
I 3
I 1
Return
(common)
I 15
I 14
Range JMPR
Jumper
Wire
Auxiliary
Terminal Strip
or Shorting Bar
Terminal A
Connections
Current
Source
Current
Source
An optional Auxiliary I/O Terminal Strip or Shorting Bar can be used for wiring
convenience, when multiple Return paths need to be wired together.
An external source must be provided to power input transceivers.