GFK-1504N Chapter 12 Analog Mixed I/O Modules 12-13
12
IC200ALG431
Analog Mixed Module, 12 Bit 0 to 10 V DC Input 4 Channels and Output 2 Channels
Jumper Selection
A jumper on the carrier can be used to select the output default mode. If no
jumper is installed on pins B13 and B14 outputs hold their last state (the last
commanded value from the backplane) if backplane power or communications
are interrupted or the PLC is stopped. With a jumper installed, if such
conditions occur outputs default to 0 V. This should only be changed with field
power and backplane power removed.
Jumper
Selects
None
Hold Last State
JMP 1
Default to 0
Wiring Examples
V Out 2
V Out RET 2
Field Power
Field Return
V Out 1
V Out RET 1
JMP 1A
JMP 1B
-
+
Shield
Shield
24VDC
Load
Load
Jumper present
selects default to 0
Voltage Inputs
V In RET 4
V In RET 1
V In 1
V In 4
Voltage Outputs
Voltage
Source
Voltage
Source
An external source is needed to
power input transceivers.