WavePro™ 3200–5000 A Power Circuit Breakers
Chapter 3. Breaker Operation
A Disconnect Block (left side from front) C Disconnect Block (right side from front)
10 Aux Switch (NO contact) 10 Aux Switch (N.O. contact)
1 Aux Switch 1 Aux Switch
2 Aux Switch 2 Aux Switch
11 Aux Switch (NC contact) 11 Aux Switch (NC contact)
12 Aux Switch (NO contact) 12 Aux Switch (NO contact)
3 Aux Switch 3 Aux Switch
4 Aux Switch 4 Aux Switch
13 Aux Switch (NC contact) 13 Aux Switch (NC contact)
5 Aux Switch (NO contact) 14 Second Shunt Trip
6 Aux Switch (NC contact) 5 Second Shunt Trip
2
7 Aux Switch (common)
2
OR
OR 14 Aux Switch (NO contact)
5 Shunt Trip (NO contact) 5 Aux Switch
2
6 Shunt Trip (NC contact)
7 Shunt Trip (common)
2
6 Aux Switch
14 Bell Alarm (NO contact) 15 Aux Switch (N.C. contact)
15 Bell Alarm (NC contact) 8 Remote Charge Indicator
16 Bell Alarm (common) 17 Remote Charge Indicator
19 Bell Alarm (NO contact) 16 Spare
20 Bell Alarm (NC contact) 7 Spare
21 Bell Alarm (common) 9Spare
8 Closing Spring Charging Motor 18 Spare
17 Closing Spring Charging Motor 19 Spare
9Close Circuit
1
20 Spare
18 Close Circuit
1
21 Spare
22 Undervoltage or Electric Lockout 22 OFLO (phase A)
23 Undervoltage or Electric Lockout 23 OFLO (phase A)
24 Neutral Sensor – tap 24 OFLO (phase B)
25 Neutral Sensor – common 25 OFLO (phase B)
26 Commnet+ 26 OFLO (phase C)
27 Commnet– 27 OFLO (phase C)
28 Zone Selective Interlock (In+) 28 Spare
29 Zone Selective Interlock (In–) 29 Spare
30 Zone Selective Interlock (Out+) 30 Spare
31 Zone Selective Interlock (Out–) 31 Spare
32 Va (voltage conditioner) 32 Spare
33 Vb (voltage conditioner) 33 Spare
34 Vc (voltage conditioner) 34 Spare
35 Trip Unit Aux Pwr (24 Vdc+) 35 Spare
36 Trip Unit Aux Pwr (24 Vdc–) 36 Spare
1
For electrically operated breaker; Remote Close accessory on manually operated breaker.
2
Auxiliary Switch contacts are wired out if Shunt Trip is not provided.
Table 3. Secondary disconnect terminals and standard connections.