3 | Areas of application
The compressors are factory-lled with the following oil type:
- for R134a, R404A/R507, R407C FUCHS Reniso Triton SE 55
- for R22 FUCHS Reniso SP 46
Compressors with ester oil charge (FUCHS Reniso Triton SE 55) are marked with an X in the type
designation (e.g. FKX30/325 N).
3.1 Refrigerants
HFKW / HFC: R134a, R404A/R507, R407C
(H)FCKW / (H)CFC: R22
3.2 Oil charge
ATTENTION Compressor operation is possible within the limits of application
showninthediagrams.Pleasenotethesignicanceoftheshaded
areas. The limits of application must be observed. Thresholds
should not be selected as design or continuous operating points.
- Max. permissible discharge end temperature: 140°C
- Max. permissible ambient temperature: 100°C
-Max.permissibleswitchingfrequency:12x/h
-A minimum running time of 2 min. at equilibrium (continuous
operation) must be achieved.
Avoid continuous operation near the threshold. Should the com-
pressor happen to be used near the thresholds, we recommend the
useofathermalprotectionthermostat(Accessories,Chap.7).
When operating in the vacuum range, there is a danger of air en-
tering on the suction side. This can cause chemical reactions, a
pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!
3.3 Limits of application
INFO
For recharging, we recommend the above oil types. Alternatives are:
see lubricants table, Chapter 6.6.