Fixed sequence yes/ no
"yes" means a fixed start sequence, "no" means running hours are
equalised
Master process value yes/ no If "yes" then the Master process value will be sent to all Slaves
Auto start delay secs
Used to start next compressor in sequence, initiated by process
value rising above sequence neutral zone
Switch delay secs
Delay before switching between compressor forced or held at Part
Load or Maximum position and controlling compressor
Auto stop delay secs
Used to stop next compressor in sequence, initiated by process
value falling below sequence neutral zone
Neutral zone K
Used to start and stop compressors in sequence, must be larger
than local control neutral zone (see 1.1).
1
The value refers to the combination of active cylinder or the control slide position and speed of compressor
drive motor.
Operating Manual | Sequence Control for Packages
GSC TP
Parameters
GEA Refrigeration Germany GmbH | E_301510_2 | Generated 17.12.2014 13