EasyManuals Logo

GEM 1441 cPos-X Installation, Operating And Maintenance Instructions

GEM 1441 cPos-X
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
26 / 32
1434 µPos
7 Display elements
OPEN
ERROR
CLOSED
POWER
LED Designation Colour
1 OPEN Yellow
2 ERROR Red
3 CLOSED Orange
4 POWER Yellow
Meaning Error number
LED 1
OPEN
LED 2
ERROR
LED 3
CLOSED
LED 4
POWER
Position reached
-
m m m l
Valve in OPEN end position
-
l m m l
Valve in CLOSED end position
-
m m l l
Valve moves in OPEN direction
-
I m m l
Valve moves in CLOSED direction
-
m m I l
Positioner in initialisation phase
-
I m I l
Set value > 20.5 mA / 10.25 V Error no. 1
I b m l
Set value < 3.5 mA Error no. 2
m b I l
Positioner not initialised Error no. 3
I b I l
Positioner not calibrated Error no. 4
l l l I
Device error Error no. 5
m b m l
Positioner works with lower quality Warning no. 1
Z l
Key LED conditions Flashing frequency
m
LED off
l
LED on
Z
LED flashes briefly f = 1.66 Hz; 0.15 s on / 0.45 s off
b
LED flashes fast f = 3.33 Hz; 0.15 s on / 0.15 s off
I
LED flashes slowly f = 1.66 Hz; 0.30 s on / 0.30 s off

Table of Contents

Other manuals for GEM 1441 cPos-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GEM 1441 cPos-X and is the answer not in the manual?

GEM 1441 cPos-X Specifications

General IconGeneral
BrandGEM
Model1441 cPos-X
CategoryValve Positioners
LanguageEnglish

Related product manuals