2006.05.15 1
INDOOR UNIT
H x W x D
H x W x D
320 x 998 x 228 mm
OUTDOOR UNIT
830 x 900 x 330 mm
DIMENSIONS
INDOOR UNIT
GROSS / NET
GROSS / NET
18 kg / 14 kg
OUTDOOR UNIT
70 kg / 62 kg
WEIGHT
SPECIFICATIONS
TYPE
COOL & HEAT INVERTER
INDOOR UNIT
OUTDOOR UNIT
ASHA30LCC
AOHR30LCT
COOLING CAPACITY
HEATING CAPACITY
POWER SOURCE
230 V
FREQUENCY
50 Hz
RUNNING CURRENT
COOLING
HEATING
INPUT WATTS
COOLING
HEATING
E.E.R.
COOLING
COP
HEATING
MOISTURE REMOVAL
AIR CIRCULATION-High
1,100 m
3
/hr
8.00 kW
9.00 kW
11.7 A
11.6 A
2.66 kW
2.64 kW
3.01 kW/kW
3.41 kW/kW
3.4 L/hr
FAN MOTOR
TYPE
Hermetic type, 4 pole,
DC inverter motor, Rotary
DISCRIMINATION
5KD240XAD21
REFRIGERANT
R410A
2,100 g
POWER SOURCE
230 V
HIGH-SPEED
1,330 r.p.m.
INDOOR UNIT
MED-SPEED
1,120 r.p.m.
LOW-SPEED
940 r.p.m.
QUIET
Cool
Heat
830 r.p.m.
OUTDOOR UNIT
900 r.p.m.
850 r.p.m.
ELECTRICAL DATA
COMPRESSOR
INDOOR UNIT
OUTDOOR UNIT
Cool 47 dB / Heat 45 dB
Cool 53 dB / Heat 55 dB
NOISE LEVEL
REFRIGERANT (R410A)
PIPE LENGTH
20 m
2,100 g
FULL CHARGE AMOUNT
50 m
3,300 g
ADDITIONAL REFRIGERANT
40 g / m

Related product manuals