10. Safety devices
Indoor unit
type
Model name PCB* fuse Fan motor thermal protector
Terminal
thermal
fuse
Float
switch
Compact
cassette
AUXG07KVLA
250 V, 5 A
Activate: 100 ±15 °C
Fan motor stop
Reset: 95 ±10 °C
Fan motor restart
AUXG09KVLA
AUXG12KVLA
AUXG14KVLA
AUXG18KVLA
AUXG22KVLA
Mini duct
ARXG07KSLAP
Activate: 135 ±15 °C
Fan motor stop
Reset: 105 ±15 °C
Fan motor restart
ARXG09KSLAP
ARXG12KSLAP
ARXG14KSLAP
ARXG18KSLAP
Slim duct
ARXG07KLLAP
ARXG09KLLAP
ARXG12KLLAP
ARXG14KLLAP
ARXG18KLLAP Activate: 135 ±15 °C
Fan motor stop
Reset: 115 ±15 °C
Fan motor restart
Medium static
pressure duct
ARXG22KMLB
Wall mounted
ASHG07KGTB
250 V, 3.15 A
Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
102 °C Off
ASHG09KGTB
ASHG12KGTB Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASHG14KGTB
ASHG18KMTB Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
ASHG22KMTB
ASHG24KMTB
ASHG07KMCC
Activate: 170
+25
-30
°C
Fan motor stop
Reset: 145
+25
-30
°C
Fan motor restart
ASHG09KMCC
ASHG12KMCC
ASHG14KMCC
ASHG07KETA
ASHG07KETA-B
Activate: 110 ±15 °C
Fan motor speed down
Reset: 110 ±15 °C
Fan motor speed recover
102 °C Off
ASHG09KETA
ASHG09KETA-B
ASHG12KETA
ASHG12KETA-B
ASHG14KETA
ASHG14KETA-B
Activate: 125 ±10 °C
Fan motor stop
Reset: 100 ±10 °C
Fan motor restart
Ceiling
ABHG18KRTA 250 V, 3.15 A Activate: 135 ±15 °C
Fan motor stop
Reset: 105 ±15 °C
Fan motor restart
108 °C Off
ABHG22KRTA 250V, 5.0 A
- 143 -