When saving, necessary services are started. After finishing this process, a new BACS menues will be accessible:
Hardware precondition: Connecting the BACS Bus Converter to the CS141
Even the menues are accessible, the BACS Bus Converter needs tob e connected to CS141 before starting configuration. Use the
AUX-Port of the CS141 and the COM 3 Port of the BACS Bus converter to establish a connection between the devices:
From the CS141 AUX-Port ….
… to the COM 3 port of the BACS-Bus Converter
Since the cables are coded, a wiring failure should not be possible. During installing, ensure neither to jam the connectors nor to use
brute force - the contacts may be damaged.
Once communication has been established between the
devices, a relay will click inside the BACS Bus Converter and a
red LED will light up on top, followed by a buzzer.
Press Mute to temporarily switch off the alarm. You can not
switch off the alarm permanently, after some time it will be
automatically fall back to active state.
In addition, the upper status bar inside the CS141 web interface
will show a "Communication Lost" issue - This status is normal
in this configuration state since there are no modules installed
or somthing is configured.
Using the BACS capabilities of a CS141 SC slot card
Connect the AUX-Port of the CS141 SC with COM 3 of the BACS Bus Converter. At CS141 SC, configure the COM-Ports as described.
You do not neet to restart the CS141 SC.