Mounting the BACS module at the battery
Please not the preconditions ….
- there is no dirt on the surface.
- The surface is free from fats, silicone or other coatings.
- The site is easily accessible for maintenance or subsequent service
- If possible, do not cover any valves or cooling fins
o In the case of sealed batteries, velcro tape can also be attached directly on it if there is no other way. An AGM
valves would in case of opening separate the velcro connection and the pressure escapes.
- For low maintenance batteries and wet cells, keep at least 10 cm distance to the vent pipe
Before installing the BACS modules, carefully read the installation and maintenance instructions for the corresponding battery.
Wiring the BACS module
The BACS cables are coded and standardized, an erroneous connection is normally not possible.
Connect the BACS bus cables to the modules: