Copyright of the European Union is effective (Copyright EU) (c) 2019 GENEREX Systems GmbH, Hamburg, Germany, All rights reserved
TEL +49(40)22692910 - EMAIL generex@generex.de - WEB www.generex.de (This and all other product datasheets are available for download.)
This is recommended network settings for the client PC:
IP address 10.10.10.11
subnet mask of 255.255.255.0
Gateway 10.10.10.11
DNS: none
Obey whether the settings of your service computer work by opening a console in order to enter the command
PING 10.10.10.10.
If the settings are correct, the CS141 will respond accordingly. As soon as the CS141 answers correctly, open a web browser. The
CS141 web interface will be accessible by tipping http://10.10.10.10
Adding a route
Within larger installations with well-defined domain services, it may be helpful temporarily editing the routing table.
In case of using a route, ensure the CS141 is located within the same network segment and is therefore directly accessible
Example: Adding a route into a Windows-driven Computer:
1. Run the command console cmd as administrator
This is important due to the fact, Windows requires a user with local administration rights to add a route.
2. Enter the following command: route add 10.10.10.10 <IP address of your system>
Windows will accept the command and return OK
In order to check the new rout, enter the command route print