The following table lists regular operating modes:
Initial configuration 10.10.10.10
Preparation at the CS41
Prior to commissioning, ensure the slide switch on the front is set to center position. In case of CS141Mini, both Dip switches of the
CS141 MINI has to be set in OFF position. After start up, the CS141 can be runs in configuration mode, available at IP address
10.10.10.10.
Note:
Changing the mode via the hardware switches requires a reboot of the CS141. You can perform the restart in two ways:
By removing the power supply (hardware reset)
Using the Restart feature to be found inside the Tools menu (Software Reset)
This operation does not apply the UPS the CS141 is connected to - the functionality will be kept up independently to the CS141.
Preparing the Workstation
After starting, the CS141 Web Manager can be found using the following network address:
IP address 10.10.10.10
Subnet Mask: 255.255.255.0
Depending on the type of connection you choose, the service computer can be connected directly to a crossover cable or via the local
network segment.
Sliding switch center position / DIP 1 + 2 OFF:
Enables configuration mode. After reboot the hard-coded IP address 10.10.10.10
is active.
Sliding switch to the right / Dip 1 OFF + 2 DIP 2 ON:
Automatic IP addressing: DHCP is activated and an IP address is set
automatically. Check the MAC address of your CS141 to identify the IP address in
the DHCP server table.
.
Sliding switch to he left / DIP 1 ON + DIP 2 OFF:
Use of the IP address values manually configured. If DHCP is used, the IP
address needs to be blocked for single usage.
CS141 Mini special feature:
Both Dip-Switches ON:
Enables the rescue-mode for advanced system maintenance operation.