Initial BACS Installation: Configuration of BACS
General battery data
Open the general battery configuration dialog and enter required battery data:
During installation and configuration process, you may choose between different procedures - Since each procedure comes with its
specific advantages and disadvantages:
In this case, it is up to you to decied whether first configure the BACS modules and then set the number of batteries or first configure the
number of batteries and set up the ID of the BACS modules during installation.
How to find general battery data:
Since these data are mandatory for BACS module configuration, please refer the data
sheets of the batteries as well as the name plate attached to the batteries:
In this configuration example, the voltage is 12V with a capacity of 7Ah
Nominal Battery Voltage
Define the voltage each single battery provides. Please note that you may choose between different battery models as lon as the
voltage is identical:
it is not possible to combine different cell voltages!
Capacity per Battery
Enter the capacity of the batteries in ampere hours. Please note that manufacturers decide how to specify this value inside datasheets.
If necessary, convert the values beforehand. This value defines the level of Equalization:
According to the AH value, the BACS modules will be allowed to roll out a maximum Equalizing:
An AH value under 150AH will limit the provided Equalizing power to the size of such smaller batteries, beyond 150AH BACS will use its
full Equalizing power which is available for this module type.