Center console
The address switch: The DIP bank "Address"
In contrast to the BACS modules, the GX_R_AUX must be configured to its own ID. This will be done via the DIP switches.
The following DIP settings are valid:
DIP 1 DIP2 DIP 3 DIP3 GX_R_AUX device ID
off off off off GX_R_AUX will be set to ID 1
ON off off off GX_R_AUX will be set to ID 2
off ON off off GX_R_AUX will be set to ID 3
ON ON off off GX_R_AUX will be set to ID 4
Please note that the ID, like a BACS module, requires a unique ID, which must be set consecutively starting with ID 1. The difference to
the BACS module is that the GX_R_AUX ID is set directly via the DIP bank and can not be managed via the BACS Web Manager -
whereby the base address range used differs from the BACS modules.
Therefore, the BACS module with the ID 1 cannot be confused with the GX_R_AUX ID 1.
Connecting the GX_R_AUX to the BACS Bus
The GX_R_AUX can be used everywhere inside a BACS bus - Simply connect the module between two BACS modules. The
GX_R_AUX fits seamlessly into the BACS bus and can be used immediately.
Output connectors
Screwed connectors 15-28
The ports 15-28 are on the side marked as output. Terminal 15 is in direct view from the top on the left side, in opposition to input 1.
Screwed connectors 15 - 28
15. Relay contact 1 No*
16. Relay contact 1 NC**
17. Relay contact 1 Common
18. Relay contact 2 NO*
19. Relay contact 2 NC**
20. Relay contact 2 Common
21. Relay contact 3 NO*
22. Relay contact 3 NC**
23. Relay contact 3 Common
24. Relay contact 4 NO*
25. Relay contact 4 NC**
26. Relay contact 4 Common
27. Relay contact zukünftige Entwicklungen
28. Relay contact zukünftige Entwicklungen
*NO: normally open contact
**NC: normally closed contact