Note
If the labels and labels have been removed, you can still clearly identify the numbering of the screw terminals based on the position of
the LEDs: On one side you have 5 LEDs - 4 grouped and one separated. The separate LED is the status indicator.
Align the GX_R_AUX in a way that the 5 LED's are in the upper side.
From now, you can easily numerate the terminals you are looking for:
The upper screw bar is numbered from left to right in ascending order, the first connection on the left
outside defines 1. Furthermore, the upper bar defines the input bar.
The DIP switches are numbered from left to right in this orientation, from left to right: 1, 2, 3, 4
The bottom screw bar starts on the left side with the number 15 and is incremented to the right
continuously. the bottom screw bar defines the outputs
GX_R_AUX Configuration guide
For this configuration step, navigate to the following menu:
Step 1 - Setting up a mandatory GX_R_AUX ID
Set up a corresponding ID - the ID's you choose hast to start with 1 and ends with a number according to the number of GX_R_AUX
you wish to use. Please note the following conditions:
- An ID may only be assigned once
- The first device receives the ID 1, then it is consecutively numbered
- Do not use more than the maximum of 4 GX_R_AUX within one BACS installation.
Step 2 - At BACS Webmanager, open the GX_R_AUX configuration dialog
In the configuration dialog, you can use the BACS Webmanager to specify the number of installed modules:
Enter "0" to disable the function. Otherwise, set the number of used GX_R_AUX modules and click Apply. Due to the fact new devices
have been added to the BACS bus, the web manager must reboot BACS to find and initialize the new devices accordingly. This
procedure will only restart required services, neither the Webmanager itself nor the UPS will reboot.
Note
The BACS Webmanager will program the ID of a GX_R_AUX - the ID will be set by the DIP switch bank. After setting up the hardware
ID of the GX_R_AUX, the Webmanager will be configurated to search for the specific number of GX_R_AUX that are placed inside the
BACS installation. If the estimated number of GX_R_AUX is not found, a corresponding error message will occur.
You can follow the success of the initialization in the upper task bar.