How to set up the outputs of a GX_R_AUX as battery breaker
Under Thermal Runaway, activate the battery breaker functionality
Before configuring the GX_R_AUX outputs and associated events, you need to decide if and how many battery breakers you need.
Open the Thermal Runaway configuration dialog - the battery breaker configuration is mostly done automatically, which manifests itself
in subsequent configurations:
1. According outputs will be labeled automatically
2. Events and jobs assigned to a Thermal Runaway are automatically entered
The total number of required battery breaker depends on the number of strings you configured at BACS general setup.
If you want to use one battery breaker for the complete installation, select the option Trip
single Battery-Breaker for all strings “.
If you want to use a single battery breaker for each string installed in your BACS
System, select the option „Trip separate Battery-Breaker for each string
Press Apply when ready.
Under Setup GX_R_AUX, you will find new entries:
As you can see, BACS auto-labeled your GX_R_AUX Outputs according to your settings. You cannot re-label them - they are reserved
for the battery breakers. Please note: If you use battery breaker, ensure, the NC Contact Flag is not set!
Again, press Apply when ready
How the BACS Webmanager will count the battery breaker:
The first battery breaker will be associated with output 1. From there onwards, all battery breaker will be counted one by one. If several
AUX are in use, the 5th battery interrupter is configured on the 2nd AUX, Port 1. The classification as battery breaker will exclude any
existing configuration - the configured output can only be used for the according battery breaker. Furthermore, depending on the
number of GX_R_AUX devices, an individually configured additional configuration dialog will appear:
Name the inputs and outputs in free text. Theses labels can be found next to the inputs and outputs at the GX_R_AUX - Monitor:
Normally Open / Normally Closed
If you do not use battery breaker you may use the outputs freely. Depending on your settings, the behavior of the BACS Webmanager
changes when dealing with contacts:
NC / NO input configuration
The inputs provide to connect any potential-free switch contacts. It can be distinguished whether a contact must normally be closed
(NC) or open (NO). By Changing from NO to NC behavior, it is possible to harmonize the contacts to third party devices.