A switching state in opposition to the configuration is provided with a red alarm marker:
In this case, the climate control will close the contact if running. Otherwise the Status is marked red – the climate control is off.
NC / NO output configuration
The outputs can be assigned via the terminal strips 15-26. This option defines if a contact is generally closed and needs to be opened or
open and has to be closed. During the BACS initialization, the switches automatically take the correspondingly configured switching
states.
Please note:
A NO - normally open - contact is open at system startup and must be closed /turned on accordingly:
An NC - normally closed - contact is closed at start up and must be switched to off / open accordingly
Depending on the configuration, the marker is green (active) or grey (disabled).
Defining jobs to GX_R_AUX input events
BACS use a stand-alone event and job management.
This allows to use a BACS system completely without a UPS connection in stand-alone operation and use its own sensors.
To define a job, open the events menu in the BACS configuration menu and search for the following entry:
BACS GX_R_AUX 1 defines the module assigned with the ID 1 via the DIP bank. If you have more modules in use, they will be listed
automatically as AUX 2, AUX 3, and AUX 4 inside the event menu.
The current alarm ON/Off state will be determined by NO / NC contacts definition at GX_R_AUX setup. At the event handling, it is
possible to configure what will happen at the current contact state.
Note
The word "alarm" itself is relative meaning in this context. You can also communicate with other devices through the inputs and, for
example, get switching confirmations - you are not forced to use this as an "alarm" notification.
Setting up a job
In this example, a log entry job is set to Input Port 1.