EasyManua.ls Logo

Generex CS141 - Page 187

Generex CS141
320 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Version: 2020-09-04
187
Copyright of the European Union is effective (Copyright EU) (c) 2019 GENEREX Systems GmbH, Hamburg, Germany, All rights reserved
TEL +49(40)22692910 - EMAIL generex@generex.de - WEB www.generex.de (This and all other product datasheets are available for download.)
To enter a new job, select + at Input 1 Alarm this will open the job configuration dialog:
1. As Job, choose „Log “:
With the job type, the parameters will be adapted automatically. In this case, you can type a free text messages that will appear at the
event log if GX_R_AUX 1 input port 1 reports a closed alarm contact position:
Timing will allow to define when this job shall be executed. In this case, the job is executed once, at the precise moment when the
defined alarm behavior occurs. For more information, please refer to the chapter event handling at part 1 of this manual.
With save, the job will be written to the configuration file and executed as soon as the according event occurs. You do not need to
restart the CS141 / BACS Webmanager.
Checking the job configuration:
To test the job, unfold the event BACS GX_R_AUX 1 Input 1 Alarm by clicking
Your new job will be displayed:
At this menu, you can edit, delete or test the job. More information can be found at event handling configuration in part 1 of this manual.
Communicate with third party devices via GX_R_AUX outputs
In this example, a third-party monitoring device shall be triggered by AUX output port 1.
1. Choose the event that shall trigger the output and press to start the job configuration dialog
2. As job, choose AUX:
Depending on the number of installed GX_R_AUX modules, you can select an individual port from the list:
In this example, GX_R_AUX 1, Port 3 is selected.
By doing so, use at GX_R_AUX output screw bar these screw connectors:
21 Relay contact 3 NO*
22 Relay contact 3 NC**
23 Relay contact Common
The wiring method determines what will happen in case of the command „Set High (On) “:

Other manuals for Generex CS141

Related product manuals