Address
Type
Function
Name
Description
Length
99
U
3 / 4
OUTPUT_VOLT2
Output Voltage Phase 3 in V
1
100
U
3 / 4
OUTP0WER0
Outpower Phase 1 %
1
101
U
3 / 4
OUTP0WER1
Outpower Phase 2 %
1
102
U
3 / 4
OUTP0WER2
Outpower Phase 3 %
1
103
U
3 / 4
BATTCAP
Battery Capacity %
1
104
S
3 / 4
INVOLT0
Input Voltage Phase 1 V
1
105
S
3 / 4
INVOLT1
Input Voltage Phase 2 V
1
106
S
3 / 4
INVOLT2
Input Voltage Phase 3 V
1
107
S
3 / 4
TEMPDEG
Temperature C°
1
108
S
3 / 4
AUTONOMTIME
Autonomy Time minutes
1
109
U
3 / 4
STATUS
UPS Status (ASCII HEX) Please note UPSMAN
status bytes table below
(e. g. UPS normal = “4”, Powerfail = “12”,
Battery test running = “68”, Bypass = “5” )
1
110
S
3 / 4
BATTVOLT
Battery Voltage V
1
111
U
3 / 4
INFREQ0
Input Frequency Hz Phase 1
1
112
U
3 / 4
INFREQ1
Input Frequency Hz Phase 2
1
113
U
3 / 4
INFREQ2
Input Frequency Hz Phase 3
1
114
U
3 / 4
CNT_PF
Powerfail Counter
1
115
U
3 / 4
Alarm Battery Bad
1 = active; 0 = not active
1
116
U
3 / 4
Alarm: On Battery
1 = active; 0 = not active
1
117
U
3 / 4
Alarm: Battery Low
1 = active; 0 = not active
1
118
U
3 / 4
Alarm: Battery Depleted
1 = active; 0 = not active
1
119
U
3 / 4
Alarm: Over temperature
1 = active; 0 = not active
1
120
U
3 / 4
Alarm: Input Bad
1 = active; 0 = not active
1
121
U
3 / 4
Alarm: Output Bad
1 = active; 0 = not active
1
122
U
3 / 4
Alarm: Output Overload
1 = active; 0 = not active
1
123
U
3 / 4
Alarm: On Bypass
1 = active; 0 = not active
1
124
U
3 / 4
Alarm: Bypass Bad
1 = active; 0 = not active
1
125
U
3 / 4
Alarm: Output Off as requested.
1 = active; 0 = not active
1
126
U
3 / 4
Alarm: UPS Off as requested.
1 = active; 0 = not active
1
127
U
3 / 4
Alarm: Charger Failed
1 = active; 0 = not active
1
128
U
3 / 4
Alarm: UPS Output Off
1 = active; 0 = not active
1
129
U
3 / 4
Alarm: UPS System Off
1 = active; 0 = not active
1
130
U
3 / 4
Alarm: Fan Failure
1 = active; 0 = not active
1
131
U
3 / 4
Alarm: fuse failure
1 = active; 0 = not active
1
132
U
3 / 4
Alarm: general fault
1 = active; 0 = not active
1
133
U
3 / 4
Alarm: diagnose test failed
1 = active; 0 = not active
1