v.: 2020-09-04
Copyright of the European Union is effective (Copyright EU) (c) 2019 GENEREX Systems GmbH, Hamburg, Germany, All rights reserved
TEL +49(40)22692910 - EMAIL generex@generex.de - WEB www.generex.de (This and all other product datasheets are available for download.)
88
Address
Type
Function
Name
Description
Length
134
U
3 / 4
Alarm: communication lost
1 = active; 0 = not active
1
135
U
3 / 4
Alarm: awaiting power
1 = active; 0 = not active
1
136
U
3 / 4
Alarm: shutdown pending
1 = active; 0 = not active
1
137
U
3 / 4
Alarm: shutdown imminent
1 = active; 0 = not active
1
138
U
3 / 4
Alarm: test in progress
1 = active; 0 = not active
1
139
U
3 / 4
AUX Port 1
1 = active (high), 0 = not active (low)
1
140
U
3 / 4
AUX Port 2
1 = active (high), 0 = not active (low)
1
141
U
3 / 4
AUX Port 3
1 = active (high), 0 = not active (low)
1
142
U
3 / 4
AUX Port 4
1 = active (high), 0 = not active (low)
1
143
U
3 / 4
Sensormanager/SMTCOM
sensor 1
Analog value
1
144
U
3 / 4
Sensormanager/SMTHCOM
sensor 2
Analog value
1
145
U
3 / 4
Sensormanager sensor 3
Analog value
1
146
U
3 / 4
Sensormanager sensor 4
Analog value
1
147
U
3 / 4
Sensormanager sensor 5
Analog value
1
148
U
3 / 4
Sensormanager sensor 6
Analog value
1
149
U
3 / 4
Sensormanager sensor 7
Analog value
1
150
U
3 / 4
Sensormanager sensor 8
Analog value
1
151
U
3 / 4
INCURR0
Input Current Plase 1
1
152
U
3 / 4
INCURR1
Input Current Plase 2
1
153
U
3 / 4
INCURR2
Input Current Plase 3
1
154
U
3 / 4
OUTFREQ0
Output Frequency Phase 1
1
155
U
3 / 4
EX_OUT_CURR0
External Output Current Phase 1
1
156
U
3 / 4
EX_OUT_CURR1
External Output Current Phase 2
1
157
U
3 / 4
EX_OUT_CURR2
External Output Current Phase 3
1
Section MHD Modular / Multimatic Modular / AEG Protect 1. Modular, ENIGMA
Address
Type
Function
Name
Description
Length
100
U
3 / 4
OUTPOWER0
Outpower Phase 1 %
1
101
U
3 / 4
OUTPOWER1
Outpower Phase 2 %
1
102
U
3 / 4
OUTPOWER2
Outpower Phase 3 %
1
103
U
3 / 4
BATTCAP
Battery Capacity %
1
104
S
3 / 4
INVOLT0
Input Voltage Phase 1 V
1
105
S
3 / 4
INVOLT1
Input Voltage Phase 2 V
1
106
S
3 / 4
INVOLT2
Input Voltage Phase 3 V
1
107
S
3 / 4
TEMPDEG
Temperature C°
1
108
S
3 / 4
AUTONOMTIME
Autonomy Time minutes
1
109
U
3 / 4
STATUS (e. g. UPS normal =
"4", Powerfail = "12", Battery test
running = "68", Bypass = "5")
UPS Status (ASCII HEX), please note
UPSMAN status bytes table below
1