3. Setting up the CS141
All devices of the CS141 family use colons as separators for the MAC address values.:
Example:
Create multiple single jobs to power up different devices via WOL. It is not possible to set up one job with different MAC
addresses.
Note:
Since the WOL signal is sent to the MAC address of a network card, the IP address and the subnet mask do not matter, as they are
used by higher system authorities. These higher network authorities must be up and running first.The port only becomes interesting in
case of the WOL signal has to be routed across networks by a router to other network nodes. Usually port 7 or port 9 is used for this
function, but you have to keep in mind that the ports are managed by the system administrator of the network and can be freely adapted
to his preferences and security approvals. In other cases, it is possible that the network hardware may use a hard coded port number
and blocks all other signals as a kind of intrusion. In case of your WOL-Signal does not work, check the local IT infrastructure if the WOL
signal was filtered or blocked by other network devices.
UPS Shutdown definition
Why is the job UPS shutdown a little bit tricky?
A UPS performs a UPS shutdown to protect the batteries from a deep discharge. The UPS is physically shut down and turned off. The
time when a UPS performs this action or how it reacts to a triggered action by scheduler or via UPS functions already varies even
between the models within a manufacturer - in addition, each manufacturer uses its own definitions for to protect batteries. But due to
the fact the UPS has been physically turned off, counter events cannot be configured.
Configuring UPS Shutdown
Shutdown time in seconds
Defines how long the UPS should maintain operation before shutting down itself.
Restore time in seconds
When the main power supply is restored, the UPS waits for the preset value in seconds until it starts up again.
Type
With this setting the UPS will be turned off or turn on. Two different settings are possible:
1 The UPS switches off the outputs but remains in operation mode.
2 The UPS shuts down and turns off completely until the main power is restored.