How to use the job UPS Shutdown
This job cannot map both settings together.
Depending on the desired operation modes, at least two jobs are required.
As an example, it is possible to use different jobs to complete the following sequence:
- Switch off outputs after 3 minutes
- Shutdown the UPS after 4 minutes
- Turn on the UPS 2 minutes after the main power supply is restored
- Activate the outputs 15 minutes later
Note that the shutdown time and the restore time must be correctly nested for both jobs.
In this case, enter either a 1 or a 2 depending on the desired event.
Search and display jobs
The Search function is a quick method to find jobs configured within events.
The CS141 provides two basic options:
Event contains…
Search for a UPS event. By typing a part of an event all events according to the text fragment are listed.
Jobs
Lists events containing a number of jobs defined by this value. As an example, if you want to know how many events contain 3 jobs,
enter 3. All events containing this number of jobs will be listed.
Configure a Job
Press + at an event to open the job configuration dialog.
Different jobs provide different parameters to be configured
Example 1: Log Enter the text CS141 shows at Event Log?
Example 2: RCCMD execute Due to the fact RCCMD needs IP address data, the parameters will change.