The value at Threshold (high) defines the upper critical temperature limit. If this temperature is exceeded, a corresponding alarm
behavior can be triggered.
SM_T_H_COM Temperature Low
The value Threshold (low) defines the lower critical temperature limit. If this temperature is undershot, a corresponding alarm behavior
can be triggered.
SM_T_H_COM Temperature Normal
Defined by the values for the upper and lower temperature limits. If no limits are entered, any displayed temperature will be displayed as
"normal.
SM_T_H_COM Humidity High
The value is defined by Threshold (high) for the relative humidity and determines the upper critical limit for humidity. If this value is
exceeded, a corresponding alarm behavior can be triggered.
SM_T_H_COM Humidity Low
The value is defined via Threshold (low) for the relative humidity and determines the lower critical limit for humidity. If this value is
undershot, a corresponding alarm behavior can be triggered.
SM_T_H_COM Humidity Normal
Defined by the values for the upper and lower relative humidity. If no limits are entered, any displayed humidity will be displayed as
"normal".
SM_T_H_COM Connection Lost
If the connection between the CS141 and the SM_T_H_COM tears off, a corresponding alarm behavior can be triggered via this system
event.
SM_T_H_COM Connection Restored
The counter event to Connection Lost: The connection has been restored; a corresponding alarm behavior can be triggered via this
system event.
Event classification
At the sub menu Sensors, click on the menu Events:
All sensor events use the same event classification:
- Temperature / Humidity High
- Temperature / Humidity HighPreAlarm
- Temperature / Humiditiy normal
- Temperature / Humidity LowPreAlarm
- Temperature / Humidity Low
Click > to open the general job list. With +, the job configuration dialog will be triggered to add a new job to the current job list.
Note:
For detailed informationen about how to manage jobs, refer the following chapter: Managing jobs
Ein Gegenjob zuweisen
Beachten Sie bitte, dass je nach Konfiguration einige ausführbare Jobs ein sog. Gegenjob benötigen, während andere Jobs lediglich
nicht mehr ausgeführt werden müssen, weil das Ereignis nichtmehr ansteht. Dieser Job wird konfiguriert, indem es beim Eintritt in das
entsprechende neue Ereignis ausgelöst wird z.B. wird der Kontakt bei Erreichen von Temperature High automatisch geschlossen und
als Gegenevent bei Temperature normal wieder geöffnet. Unterdessen wird eine Mailbenachrichtigung so lange alle 5 Minuten
gesendet, wie das Ereignis Temperature High ansteht.
Verwechseln Sie an dieser Stelle nicht ein Gegenereignis mit einem Gegenjob das eine ist ein Ereignis, welches ansteht, das andere
der entsprechende Job, der zu einem Ereignis ausgelöst werden soll beides verhällt sich relativ zueinander.
Monitor sensors: Check configuration