6) Press the button (home/ return) to return to the previous menu.
CAUTION! The value that entered in parameters should be between within range otherwise it will not be saved.
B. Work Calendar Settings:
1) When the main switch of work calendar is enabled, the setting of start and stop time of work calendar is
effective; otherwise, it is invalid.
2) Set the start and stop time of work calendar than genset will be self-started. In other words self-start
signal will be valid.
CAUTION! The start time of the day should not be greater than or equal to the stop time. When the start and stop
time value are both “0”, this function is invalid.
C. Experiment Calendar Settings:
1) When the main switch of experiment calendar is enabled, the setting of start and stop time of working
calendar is effective; otherwise, it is invalid.
2) Set start and stop time for each day. Four groups of time can be set each day. In automatic mode with no
self-start signal, the machine will start automatically at the selected start time and stop automatically after
reaching the stop time. This function is associated with the work calendar function.
CAUTION! The start time of each group should not be later than or same with the stop time, and the time of each
group on the same day should not be crossed. For example, if the time of the first group is 14:00-17:00 on
Monday, the time of the second group should be later than 17:00. When the start and stop time value are both “0”,
this function is invalid.