Nano panel
The Nano panel is designed to meet the requirements of
EN54-2 : 1997 and EN54-4 :1997. The panel can accommodate
a loop circuit of analogue addressable devices, like fire sensors,
sounders, manual call points and interface units. The panel gives
local visual and audible indications of system events means of
indicators, a message display and an integral sounder. An
integral mains derived supply provides power to the panel and
the loop circuit in normal conditions and the integral batteries
provides a standby supply for up to 24 hours with 0.5hours of
alarms should the mains supply fail. The controls are PIN code
protected. The panel is designed for surface and semi flush
mounting and facilitates both rear and top cable entry points.
Features
¨
Single loop fire control panel.
¨
Up to 127 addressable devices can be connected to a
loop circuit, devices like sensors, call point and
interface units.
¨
Two master alarm circuits.
¨
RS485 Port to connect to repeat indicator panel(s).
¨
RS232 Port to connect to an external printer.
¨
USB Port to connect to a Commissioning computer.
¨
Fire Output - One set of clean voltage-free change over
contacts.
¨
Fault Output - One set of clean voltage-free change
over contacts.
¨
Class Change input that actions class change signal to
selected sectors
¨
Evacuate input that actions all alarm sounders
including master alarms and fire output
¨
Standby supply to power the system via batteries for
24 hours plus 0.5 hour alarm load.
¨
Alphanumeric LCD with back light to display event
information.
¨
Integral 16 zone LEDs (with First fire zone LED
flashing).
¨
LED lights for event indications.
¨
Local audible buzzer for event announcement.
¨
Push buttons for essential controls and menu driven
commands.
Nano System
by Honeywell
POWERFAULT
FIRE
Tes t
Delay
Verify
Sounder Fault
Zone 2
Zone 6
Zone 10
Zone 14
Zone 3
Zone 7
Zone 11
Zone 15
Zone 4
Zone 8
Zone 12
Zone 16
Disablement
Zone 1
Zone 5
Zone 9
Zone 13
System Fault
Sound
Alarms
Silence
Alarms
Power Fault
Reset
Cancel
Buzzer
Sounder
Disablement
042bc
EN54 Parts 2 & 4
www.acornfiresecurity.com
www.acornfiresecurity.com
Question and Answer IconNeed help?

Do you have a question about the Gent Nano panel and is the answer not in the manual?

Gent Nano panel Specifications

General IconGeneral
BrandGent
ModelNano panel
CategoryControl Panel
LanguageEnglish