By pressing “OK”, the control system reverts to the main
menu and the text changes to English. Now all text in
the display appear in English. If, instead, the set point
is adjusted to “2”, all text in the display will be shown in
German.
When the desired language has been selected, enter the
main menu once again and change to the next operating
point by pressing “Arrow down”.
If you wish to ick through the pages of the operating
menu, you may press “Enter” to change the whole page
to the next set of menu points.
If you wish to return to the previous operating point, you
may press “Arrow up”.
If you wish to leave the operating menu, press “Exit”.
The operating menu will automatically shut down and
return to the main menu if no button has been touched for
app. 60 seconds, while in the operating menu.
1.3 Operating menu
>>Language
2 Room temperature
3 Not in use
4 Not in use
Set point
Operations menu
Exit OK < >
0
1: Language
There is a choice of four languages
Set point 0 = Danish, 1 = English, 2 = German, 3 = Polish
2: Room temperature
The desired room temperature may be set between
10 - 30°C.
(The room sensor is installed in the control panel).
3: Not in use
Set point must be 10
4: Not in use
Set point must be 0,0
>>Not in use
6 Cooling ON
7 Cooling
8 Min.cooling ON
Set point
Operations menu
Exit OK < >
0
5: Not in use
Set point must be 0,0
6: Cooling ON
Units of type VP (not tted with automatic cooling) must
have their set point adjusted to 0. On units with automatic
cooling, the set point may be set to 1 if you wish for the
unit to perform cooling during the summer.
7: Cooling
To prevent cooling switching in as soon as there is no
further need for heat, please set the °C room temperature
higher than the desired room temperature, before cooling
must start. (Cooling costs money).
8: Min.cooling ON
To prevent the unit from starting to cool during the
winter, regardless of how high the room temperature is,
the set point may be adjusted to the desired minimum
outdoor temperature, before the cooling function starts.
It is recommended that the temperature is set to a
minimum of 15°C. The set point for the minimum external
temperature may be set between 0 - 20°C.
>> Constant ON
10 Constant
11 Reduce ON
12 Reduce sup. Air
Set point
Operations menu
Exit OK < >
0
9: Constant ON
If other heating systems of the house are not connected
with the heat pump unit, or if there is a re place, it may
occur that the other heating systems, may stop the
operation of the heat pump. The result of this: the heat
pump unit with heat exchanger only blows pre-heated
air into the living rooms, causing increasing draught
problems as the weather gets colder outside. Units
without heat exchanger will blow external air directly
into the house. By adjusting the set point to 1, the room
sensor will be deactivated and the heat pump will be in
constant use and blow in warm air when the external
temperature is below the set minimum temperature in
point 10. If the set point is adjusted to 0, the room sensor
will regulate the heat pump regardless of the outside
temperature.
10: Constant
If constant ON is activated, this ambient air temperature
setting dictates the unit to change to constant operation if
the actual ambient temperature is lower than the outside
temperature.
The set point may be set between 0° - 10° C.
11: Reduce ON
At very low ambient temperatures, it may be an
advantage to reduce the supply air volume in order
to improve the operating conditions of the heat pump
and simultaneously achieve a higher supply of air
temperature. By adjusting the set point to 1, the supply
air volume will be reduced when the external temperature
falls below the set temperature. If the set point is adjusted
to 0, there will be no reduction of supply air volume
regardless of the outside temperature. This setting is for
use when a preheating surface has been mounted on the
fresh air supply.