Settings GC 339
22
BASIC menu
0 1 2 3 4 5 6 7 8 9
Back
Continue
Comfort
default settings
Standard
1
Dicult
cond.
2
Shopping
street
3
1
Factory settings
2
Increased immunity lter + 1 curtain
3
Increased immunity lter + diversion = movement and presence
Not permitted for FR doors!
AIR: Filter
< 2.8 m > 2.8 m
To ensure compliance with EN16005
and DIN18650, the values 6 and 7 must
be selected for an installation height of
2.8m or more.
low normal high
higher highest normal high
not compliant with
DIN18650 / EN16005
Inside Outside
AIR: Frequency
A B
Use dierent frequencies for sensors which have been installed
next to or above one another.
Back / Continue
ADVANCED menu
0 1 2 3 4 5 6 7 8 9
Back / Continue
AIR: Width
In addition, always use a screwdriver to set the arrows for eld width on the detector.
AIR: Number
Service
mode
1 2
Service mode = no presence detector for 15 minutes (during maintenance).
This value does not permit conformity of the door system with EN 16005 and DIN 18650.
AIR: Max. time
Movem. 15 sec.
30 sec.
1 min. 2 min. 5 min. 10 min. 20 min. 60 min. endless
Minimum value for DIN 18650: 1 min
Minimum value for EN 16005: 30 sec