26
4000123942-2
11659
CONTROL PANEL USER INTERFACE
RETAINING LATCHES
11974
Diagram 11.3
11.3 Mains Voltage External Controls
WARNING: UNDER NO CIRCUMSTANCES MUST ANY
MAINS VOLTAGE BE APPLIED TO ANY OF THE TERMINALS
ON THE VOLTAGE FREE HEATING CONTROLS
CONNECTION TERMINAL.
When mains voltage external controls are used, remove the
MAINS VOLTAGE HEATING CONTROLS CONNECTION PLUG
from the fittings pack and install on the control interface PCB
as follows.
Gain access to the control interface by unclipping the fascia
panel and hinging forward, see diagram 11.3.
Route the external heating controls cable (not supplied) and
connect to the plug
, see diagram 11.3.
Insert plug onto controls interface PCB, see diagram 11.3.
Close the fascia panel and remove the screws to open the rear
cover of control panel, see diagram 11.1.
Secure the external heating control cable in the strain relief, and
thread the cable through rear of the control panel and out of the
cables exit, see diagram 11.4.
Close and secure rear cover of control panel.
IMPORTANT: Remove the wire link from the voltage free
heating controls connector terminal, see diagram 11.1.
Connect external heating controls as diagram 11.5.
External controls should be fitted in accordance with the rules
in force.
11.4 Electrical Connections - Testing
Carry out preliminary electrical system checks as below:
1. Test insulation resistance to earth of mains cables.
2. Test the earth continuity and short circuit of cables.
3. Test the polarity of the mains.
230V~ 50Hz
PERMANENT
MAINS
SUPPLY
3 AMP FUSE
DOUBLE POLE
ISOLATOR
EXTERNAL
JUNCTION BOX
LNE
EXTERNAL
FROST
THERMOSTAT
EXTERNAL
ROOM
THERMOSTAT
DO NOT
CONNECT
X
INTERNAL PROGRAMMER
EXTERNAL 230V AC ROOM THERMOSTAT
EXTERNAL 230V AC FROST THERMOSTAT
3
2
REMOVE LIN
HEN EXTERNAL
CONTROLS ARE SE
TO MAIN PCB
CONNECTOR J5
VOLTAE FREE
HEATIN CONTROLS
CONNECTION
ON CONTROLS
BOX COVER
MAINS VOLTAE
HEATIN CONTROLS
CONNECTION PLU
ONOFF
SITCH
CONTROLS
INTERFACE PCB
OILER
PRORAMMER
230V~ 50Hz
PERMANENT
MAINS
SUPPLY
3 AMP FUSE
DOUBLE POLE
ISOLATOR
EXTERNAL
JUNCTION BOX
LNE
EXTERNAL
FROST
THERMOSTAT
EXTERNAL
ROOM
THERMOSTAT
DO NOT
CONNECT
X
EXTERNAL PROGRAMMER/CLOCK
EXTERNAL 230V AC ROOM THERMOSTAT
EXTERNAL 230V AC FROST THERMOSTAT
3
2
REMOVE LNK
HEN EXTERNAL
CONTROLS ARE SE
TO MAIN PCB
CONNECTOR J5
EXTERNAL
PRORAMMER
VOLTAE FREE
HEATIN CONTROLS
CONNECTION
ON CONTROLS
BOX COVER
MAINS VOLTAE
HEATIN CONTROLS
CONNECTION PLU
ONOFF
SITCH
CONTROLS
INTERFACE PCB
OLER
11993
EXTERNAL
CONTROLS
CABLE(MAINS
VOLTAGE)
11992
STRAIN
RELIEF
EXTERNAL
CONTROLS
CABLE
MAINS
CABLE
Diagram 11.4
Diagram 11.5
11 Electrical Connection
PLUG
CONTROLS
INTERFACE PCB
The type of plug and
orientation may be
different to that
illustrated but the
wiring should always
be as wiring diagrams