INSTALLATION
13 Speci c adjustment
13.1 Venting the HP circuit
The venting of the HP circuit allows you to purge any air in the
HP circuit.
Ø14
A
B
1
3
4
1
2
Key
1 Air trap
2 Ø 14 mm at wrench (*)
3 Hose
4 Container (*)
(*) Not included
Connect one end of the hose (3) to the trap (1).
Insert the other end of the hose (3) into the container (4) in
order to recover any residual glycol during the venting of the
circuit
Begin the venting process with the control unit.
• Using a at wrench (2), open the trap (1) a ¼ turn in order to
remove the air present in the glycol circuit, then close it quickly
(in order to avoid emptying the circuit).
Repeat this last operation at the end of the venting procedure.
b
The venting may result in a drop in the glycol
circuit pressure.
Ensure that the glycol circuit pressure is between 1.5 and
2bars. If it not, top up the glycol circuit.
b
When venting is complete, make sure that the
various heating circuit air vent are open.
13.2 Adjustment of HP circuit ow
The heat pump is designed to operate with a minimum ow of
750 l / h. If the ow is less than 500 l / h, the heat pump will stop
and the boiler will begin to function. Heating comfort will always
be guaranteed, but energy saving will be compromised.
The heat pump is equipped with a ow sensor and it is possible
to read the water ow directly via the control unit.
i
The HP circuit ow should be between 750 and 850 l / h.
i
Incorrect venting of the installation may lead to
variations in ow.
If you are unable to obtain a ow of between 750 and 850l/h
using the ow control valve of the hydraulic module, change
the speed of the heat pump module.
2
3
1
Key
1 Speed control
2 Speed I
3 Speed II (not applicable to this system)
Available pressure in the heat pump circuit
60
50
40
30
20
10
0
300 600 900 1200
B
1 2
Key
1 With the water circuit at 20 ° C
2 With a brine water circuit (a mixture of 30%) at 20 ° C
A Available pressure (kPa)
B circuit ow rate (l/h)