Product description 2
0020288229_00 MiSet Operating and installation instructions 11
MENU → SETTINGS → Installer level → Installation configuration
→ Control: Weath.-
comp.
It is controlled via the outdoor temperature as soon
as an outdoor temperature sensor is connected.
→ Heat generator 1
→ Status:
→ Current flow temperature: °C
→ Circuit 1
→ Status:
→ Target flow temperature: °C
→ OT switch-off
threshold: °C
Enter the upper limit for the outdoor temperature. If the outdoor
temperature rises above the set value, the system control deac-
tivates heating mode.
→ Heat curve: The heat curve (→ section "Product description") is the depend-
ence of the flow temperature on the outdoor temperature for the
desired temperature (target room temperature).
→ Min. target flow tem-
perature:°C
Enter the lower limit for the target flow temperature. The system
control compares the set value with the calculated target flow
temperature, and regulates to the larger of these values.
→ Max. target flow tem-
perature:°C
Enter the upper limit for the target flow temperature. The system
control compares the set value with the calculated target flow
temperature, and regulates to the smaller of these values.
→ Set-back mode:
→ Eco The heating function is switched off and the frost
protection function is activated.
At outdoor temperatures that are below 4 °C for
longer than four hours, the system control switches
the heat generator on and regulates to the Set-
back temperature: °C. At an outdoor temperature
above 4 °C, the system control switches the heat
generator off. The monitoring of the outdoor tem-
perature remains active.
Heating circuit behaviour outside of the time peri-
ods. Prerequisite:
– Time-contr. is activated in the Heating →
Mode: function.
– Active or Inactive is activated in the Room
temp. mod.: function.
If Expanded is activated in the Room temp.
mod.:, the system control regulates to the target
room temperature 5 °C independently of the
outdoor temperature.
→ Normal The heating function is switched on. The system
control regulates to the Set-back temperature: °C.
Prerequisite: Time-contr. is activated in the Heat-
ing → Mode: function.
The behaviour can be adjusted separately for each heating circuit.
→ Room temp. mod.:
→ Inactive