EasyManua.ls Logo

Glowworm EASICOM 3 - Installation; Preparing for Installation; Installing the Heating Pump; Heating water supply in the open heating system

Glowworm EASICOM 3
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 Installation and maintenance instructions EASICOM 3 0020238431_03
7 Installation
7.1 Preparing for installation
Make sure that the existing gas meter and the pipelines
are capable of passing the rate of gas supply required.
Consider the maximum heat output given in DHW mode.
Install the following components:
Draining cocks at the lowest points in the heating
installation ( current version of "BS 2879")
A bypass that is at least 1.5 m away from the product
A stopcock in the gas pipe
Where applicable, a flow regulator valve to adjust the
flow rate
Install the connection pipes such that they are free from
mechanical stress.
If you use non-diffusion-tight plastic pipes in the heating
installation, ensure that no air gets into the heat gener-
ator circuit.
Only solder connectors if the connectors are not yet
screwed to the service valves.
Only bend connection pipes if they have not yet been
connected to the product.
Flush the heating installation thoroughly before installing
the product.
Check the leak-tightness of the gas valve assembly using
a pressure of 11 kPa (110 mbar).
7.2 Installing the heating pump
The flow rate must not fall below the value in the diagram.
Only use pumps that have an in-rush current 10/15 A.
When designing/selecting the pump, note the pressure
loss of the product.
Install the pump in the heating flow.
Install the pump upstream and downstream of the pump
isolation valves.
Set the pump so that the temperature difference between
the flow and return is no more than 20 °C when the max-
imum flow temperature is set.
The flow rate specified in the technical data is
reached.
7.3 Heating water supply in the open heating
system
Connect the product to a supply/expansion tank as
shown in the figure.
The tank must not be more than 27 m (90 ft) above
the product.
The open vent pipe must be installed with an upward
gradient and must not be blocked.
Supply pipe diameter: 15 mm
The relative positions of the pump, supply and open
vent pipe must be as shown in the figure.
Condition: Combined supply and open vent pipe
Install the line in accordance with "BS 5449".
Diameter: 22 mm

Table of Contents

Related product manuals