9
9. DEC200 STANDARD CHARGER OPERATION
CHARGE CONDITION
DISPLAY
DEFAULT
FUNCTION BUTTON DISPLAY SELECTION LED
CHARGING A A, Ph Y
TERMINATION rEdy G
TERMINATION/ FAULT CODE rEdy / F R*, G
SETTING EQUALISE EqAL for 5 seconds then default display
Charge
stage
EQUALISE CHARGE A / EqAL G*, Y
AUTO BALANCE StSt / A StSt / V G
Lobt CHARGE PERIOD Lobt / A Y*
Lobt OFF PERIOD Lobt / V
CRITICAL FAULT CODE F R
NONE CRITICAL FAULT CODE F Charge continues R*
A = Output current
F = Fault code, display will alternate with the two codes
Ph = Phase of charge i.e. 1, 2 and 3
StSt = Smart start
LoBt = low battery override
/ = Display will alternate with the two-displayed information
*= flashing LED.
NOTE: In LoBt, StSt, Equalize and Termination charge function display will only be displayed for 10 seconds, not
permanently.
# Display if due to smart start.
R: Red = Fault, flashing red is a none critical fault.
Y: Yellow = Current flowing, flashing yellow when < 2.37VPC.