68
6.2.3 button
Parameter checking :
Press first, then press to check the User parameter from d0 to d11
Code
Condition
Scope
Remark
d0
IPM mould temperature
0-120
Real testing value
d1
Inlet water temp.
-9℃~99
Real testing value
d2
Outlet water temp.
-9℃~99
Real testing value
d3
Ambient temp.
-30℃~70
Real testing value
d4
Frequency limitation code
0,1,2,4,8,16
Real testing value
d5
Piping temp.
-30℃~70
Real testing value
d6
Gas exhaust temperature
0℃~C5 (125)
Real testing value
d7
Step of EEV
099
N*5
d8
Compressor running frequency
099Hz
Real testing value
d9
Compressor current
030A
Real testing value
d10
Current fan speed
0-1200 rpm
Real testing value
d11
Error code for last time
All error code
Press first, then press to check the User parameter from P0 to P7
If needed, press second, then press or to adjust the current parameter.
(for example: Press first, then press to enter parameter P7 checking, and press second, then
press or to adjust the parameter P7 Inlet water temp. Correction from -9 to 9.)
Code
Name
Scope
Default
Remark
P0
Manual defrost
0-1
0
1 Manual defrosting mode, 0 Normal mode
P1
Working mode
1
1
1 Heating mode (Non-adjustable)
P2
Timer on/off
0-1
0
1 Timer on/off is under function
0 Timer on/off is out of
function (The setting of P5 and P6 won’t work)
P3
Water pump
0-1
0
1 Always running, 0 Depends on the running of compressor
P4
Current time
HH:MM
0000
0-23:0-59
P5
Timer on
HH:MM
0000
0-23:0-59
P6
Timer off
HH:MM
0000
0-23:0-59
P7
Inlet water temp.
correction
-99
0
Default setting: 0
NOTE: Under defrosting mode, P0=1.
After defrosting finished, it will be automatic enter Normal mode, P0=0.