12.Malfunction analysis
Common malfunction and handling method
Breaker tripped or fuse
urnt out
Both indoor and outdoo
units cannot start up
Air conditioner cannot start up
Improper setting o
temperature
Whether cooling
(heating) load is proper
Malfunction o
refrigerant flow
Poor cooling (heating)
effect
When the breaker is set ON, i
will trip at once.
When the unit is turned on, the
breaker will trip in a fe
minutes
Measure the insulating
resistance for grounding to
confirm whether there is
electrical leaka
e in the unit
Check the breaker and measure
the resistance.
o power supply
Check power supply circuit
Transmitting malfunction o
wireless remote control
Check wireless remote control
The power plug is not o
poorly connected
Check and insert the plug tightly
Wrong wiring between indoo
and outdoor unit
Check the circuit according to
the circuit diagram and correc
wrong wiring
Controller fuse is burnt out
Change controller fuse
Whether connection betwee
strong and weak current boar
Make the connecting wire firm
Whether the output wire o
transformer is firm, whethe
there is voltage output
Make the connecting wire fir
and check the output voltage
Adjust the set temperature
Check the estimated load o
cooling (heating)
Malfunction of four-way valve Replace the four-way valve
Charge refrigerant
Insufficient refrigerant volume
Replace the compressor
Malfunction of compressor
Insufficient flow volume o
valve
Open the valve completely