5.2 Installation Position and Requirement 
(1) Prohibit installing the wired controller at the misty place or the place with direct sunlight. 
(2) Prohibit  installing  the  wired  controller  at  the  place  near  high  temperature  objects  or 
water-splashing places. 
(3) Prohibit installing the wired controller at the place where faces forward to the window, to avoid 
interference of another remote controller from neighborhood. 
(4) Cut off the power of heavy current wire in the installation hole of the wall. All power should be cut 
off during installation. 
(5) In order to avoid abnormal operation due to electromagnetic interference, etc., pay attention to 
the following notes during connecting wires:   
1)  Make sure the tie-in interface of communication wire is correct, otherwise it may lead to 
communication malfunction. 
2)  The signal  wires and  communication  wires of  wired controller  should be  separated  from 
power cord and connection wire between indoor unit and outdoor unit. 
3)  If the air conditioner is installed at the strong electromagnetic interference place, signal wire 
and communication wire of wired controller must use shielding twisted wire.   
 
5.3 Installation of Wired Controller 
Firstly, the selection and connection way of wired controller‟s signal wire are as below: 
(1) Choose suitable signal wire: 2-core signal wire (wire diameter
≥
0.75mm, wire length
<
30m and 
the recommended length is 8m). 
(2) Make sure the power of indoor unit is cut off; fix the signal wire of wired controller on the wiring 
board for wired controller of indoor unit with screws; make sure the signal wire is solid. 
Then, the detailed installation procedures of wired controller are as shown in Figure 2-5-2: 
 
Figure 2-5-2 Installation of wired controller 
Brief instructions of installation procedure: 
a)  Pull out the 2-core signal wire in the installation hole of the wall and then let this wire go