DC Inverter Multi VRF System
26
7
System
parameters
ODU
parameters
Compressor
working current
—
GMV-H224WL/A-X
GMV-224WL/C-X
When compressor works
normally, the current is no
GMV-H280WL/A-X
GMV-280WL/C-X
When compressor works
normally, the current is no
GMV-H335WL/A-X
GMV-335WL/C-X
When compressor works
normally, the current is no
8
Compressor’s
IPM temp
°C
When ambient temperature is below 35°C, IPM
temperature is lower than 70°C. Maximum
9
IDU
parameters
IDU ambient temp °C —
10
Indoor heat
exchanger’s inlet
°C
According to ambient temp, for a same IDU in
cool mode, the inlet temp will be 1~7°C lower
than the outlet temp, and 4~9°C higher than the
low pressure value.
For a same IDU in heat mode, the inlet temp will
be 10~20°C lower than the outlet temp.
11
Indoor heat
exchanger’s inlet
°C
12
Opening degree
of indoor EXV
PLS
In cool mode, the opening degree of indoor EXV
varies within 40~480PLS.
In heat mode, the opening degree of indoor EXV
13
—
Number of IDUs detected by software is the same
with the actual number. No communication error.
14 Drainage system — —
Indoor unit can drain water out completely and
smoothly. Condensate pipe has no backward slope
of water; Water of outdoor unit can be drained
completely through drainage pipe.
No water drop
15 Others — —
Compressor and indoor/outdoor fan motor do not
have strange noise. Unit can operate normally.
6 Common Malfunctions and Troubleshooting
WARNING:
①
If an abnormal situation (such as peculiar smell) occurs, please stop the operation
immediately and turn off the main power supply, and then contact Gree authorized
maintenance center. If the unit continues to operate under abnormal situation, the air
conditioner will be damaged and an electric shock or fire accident may result.
②
Do not maintain the air conditioner by yourself, misoperation may cause electric shock or fire
hazard. Please contact professional personnel of Gree authorized maintenance center to
maintain.
● Before asking for maintenance, please check the following issues first.
Unit doesn’t work.
Fuse or circuit breaker is cut off.
Replace fuse or reset the circuit
breaker.
Power failure.
Restart unit when power is
Power supply is not connected
Remote controller’s power is not enough.
Remote controller is out of the control range.
Control range is within 8m.