GMV DC Inverter VRF 
51 
Description of each stage of debugging progress 
System is allocating addresses. 
Master IDU is not set. Please set 
master IDU. If it’s not set in 1min, 
system will set the master IDU 
randomly.   
Allocation is finished. Start next 
progress. 
03_Confirm the 
quantity of 
modules 
LED3 displays the quantity of modules. 
Confirm the number manually.   
System has confirmed the quantity of 
modules. Start next progress. 
04_Confirm the 
quantity of IDUs 
LED3 displays the quantity of IDUs. 
Confirm the number manually.   
System has confirmed the quantity of 
IDUs. Start next progress. 
05_Detect 
internal 
communication 
System detects “driven communication 
error between master unit and inverter 
compressor”. 
System detects “driven communication 
error between master unit and inverter 
fan”.   
IDU/ODU “high proportion of rated 
capacity”. 
IDU/ODU “low proportion of rated 
capacity”.   
Detection is finished. Start next 
progress. 
06_Detect 
outdoor 
components 
System detects error in outdoor 
components. 
No error in outdoor components. Start 
next progress. 
07_Detect 
indoor 
components 
System detects error in indoor 
components. XXXX is the project no. of 
the faulted IDU. 3s later, relevant error 
code is displayed. For example, IDU 
no. 100 has d5 error, then LED3 
displays like this: 01 (2s later) 00 (2s 
later) d5, and repeat again. 
No error in indoor components. Start 
next progress. 
08_Confirm 
preheated 
compressor 
Preheat time for compressor is less 
than 8h. 
Preheat time for compressor is 8h. 
Start next progress. 
09_Refrigerant 
judgments 
before startup 
System refrigerant is not enough. 
System downtime equilibrium pressure 
is lower than 0.3MPa.   
System refrigerant is normal. Start next 
progress.