GMV DC Inverter VRF
54
board of each module will display:
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
03_Quantity of
modules
db
light
03
light
Quantity of
modules
blink
If the quantity displayed is the same with actual quantity, then press SW7 confirmation
button on the master unit to confirm it. Unit will start next progress:
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
03_Confirm the
quantity of
modules
db
light
03
light
OC
light
If the quantity displayed is different from actual quantity, then disconnect power and check
whether communication wire among each module is correctly connected. After the check, start
debugging again.
Step 8:
in progress 04, the quantity of IDUs needs to be confirmed manually. Main board
of each module will display:
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
04_Confirm the
quantity of IDUs
db
Light
04
Light
Quantity of
connected
IDUs
blink
If the quantity displayed is the same with actual quantity, then press SW7 confirmation
button on the master unit to confirm it. Unit will start next progress:
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
04_Confirm the
quantity of IDUs
db
Light
04
Light
OC
Light
Step 9:
progress 05 is “Detect internal communication”
If no error is detected, system will display as below and then start next progress.
——
Debugging code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
05_Detect
internal
communication
db
Light
05
Light
OC
Light
Detection is finished. Start next
progress.

Table of Contents

Other manuals for Gree GMV-280WM/E1-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-280WM/E1-X and is the answer not in the manual?

Gree GMV-280WM/E1-X Specifications

General IconGeneral
BrandGree
ModelGMV-280WM/E1-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals