GMV DC Inverter VRF
55
If error is detected, system will stay at current progress. Error has to be solved manually.
Below are relevant errors:
——
Debugging code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
05_Detect
internal
communication
db
Light
05
Light
C2
Light
System detects “driven communication
error between master unit and inverter
compressor”.
db
Light
05
Light
C3
Light
System detects “driven communication
error between master unit and inverter
fan”.
db
Light
05
Light
CH
Light
IDU/ODU “high proportion of rated
capacity”.
db
Light
05
Light
CL
Light
IDU/ODU “low proportion of rated
capacity”.
Elimination methods of above errors can be found in Troubleshooting.
Step 10: progress 06 is “Detect outdoor components
If no error is detected, system will display as below and then start next progress.
——
Debugging code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
06_Detect
outdoor
components
db
Light
06
Light
OC
Light
No error is detected in outdoor
components. Start next progress.
If error is detected, system will stay at current progress. Error has to be solved manually.
Below is relevant error:
——
Debugging
code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
06_Detect
outdoor
components
db
Light
06
Light
Error
code
Light
System detects error in outdoor
components.
Elimination methods of above error can be found in Troubleshooting.
Step11:
progress 07 is “Detect indoor components”
If no error is detected, system will display as below and then start next progress.
——
Debugging code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
07_Detect indoor
components
db
Light
07
Light
OC
Light
No error is detected in indoor
components. Start next progress.
If error is detected, system will stay at current progress. Error has to be solved manually.

Table of Contents

Other manuals for Gree GMV-280WM/E1-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-280WM/E1-X and is the answer not in the manual?

Gree GMV-280WM/E1-X Specifications

General IconGeneral
BrandGree
ModelGMV-280WM/E1-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals